Differential pressure |
Measuring range | - 0 to 10 Pa
- 0 to 50 Pa
- 0 to 100 Pa
- 0 to 500 Pa
- 0 to 10 hPa
| - -10 to +10 Pa
- -50 to +50 Pa
- -100 to +100 Pa
- -500 to +500 Pa
- -10 to +10 hPa
|
Measurement uncertainty* | ±0.3% of measurement range final value±0.3 PaTemperature gain drift: 0.02% of measuringrange per Kelvin deviaton from nominaltemperature 22 °CZero point drift: 0% (thanks to cyclic zeropoint adjustment) |
Selectable units | Differential pressure in Pa, hPa, kPa, mbar, bar, mmH2O, kg/cm2, PSI, inch HG, inch H2O |
Sensor | Piezoresistive sensor |
Autom. zero-point adjustment | via magnetic valve Frequency adjustable: 15 sec, 30 sec, 1 min, 5 min, 10 min |
Overload | Measuring range - Overload- 0 to 10 Pa - 20000 Pa
- 0 to 50 Pa - 20000 Pa
- 0 to 100 Pa - 20000 Pa
- 0 to 500 Pa - 20000 Pa
- 0 to 10 hPa - 200 hPa
- -10 to 10 Pa - 20000 Pa
- -50 to 50 Pa - 20000 Pa
- -100 to 100 Pa 20000 Pa
- -500 to 500 Pa - 20000 Pa
- -10 to 10 hPa - 200 hPa
|
Analog outputs |
Quantity | Standard: 1;with optional humidity probe: 3 |
Output type | - 0/4 to 20 mA (4-wire) (24 VAC/DC)
- 0 to 1/5 to 10 V (4-wire) (24 VAC/DC)
|
Scaling | Differential pressure: scalable ±50% of measuring range final value; freely scalable within measuring range |
Meas. cycle | 1/sec |
Resolution | 12 bit |
Max. load | max. 500 Ω |
Other outputs |
Ethernet | Optional |
Relay | Optional: 4 relays (free allocation to measurement channels or as collective alarm in operating menu/P2A), up to 250 VAC/3A (NO or NC) |
Digital | Mini-DIN for P2A software |
Voltage supply | 20 to 30 VAC/DC, 300 mA current consumption, galvanically separate signal and supply line |
Material | Front plate stainless steel, housing plastic |
Dimensions | without humidity/temperature: 246 x 161 x 47 mm with humidity/temperature: 396 x 161 x 78 mm |
Weight | Version without humidity: 0.9 kg;Version with integrated humidityprobe:1.35 kg; version with preparationfor external humidity probe: 1.26 kg |
Display | 3-line LCDwith multi-language operating menu |
Differential pressure | Measuring range - Resolution- 0 to 10 - Pa 0.1 Pa
- 0 to 50 - Pa 0.1 Pa
- 0 to 100 - Pa 0.1 Pa
- 0 to 500 - Pa 0.1 Pa
- 0 to 10 hPa - 0.01 hPa
- -10 to 10 Pa - 0.1 Pa
- -50 to 50 Pa - 0.1 Pa
- -100 to 100 Pa - 0.1 Pa
- -500 to 500 Pa - 0.1 Pa
- -10 to 10 hPa - 0.01 hPa
|
Humidity (Measuring range) | 0.1 %RH |
Temperature (Measuring range) | 0.01 °C / 0.01 °F |
Protection class | IP 65 |
Connection nipple | Ø 6 mm --> suitable hoses 4 mm + 4.8 mm |
Operation temperature | -5 to +50 °C / +23 to +122 °F |
Storage temperature | -20 to +60 °C / -4 to +140 |
Process temperature | -20 to +65 °C / -4 to +149 °F |
Humidity/temperature optional |
Probe | Integrated probe | 6613 | 6614 | 6615 | 6617 |
Type | Channel | Duct heated | Cable trace humidity | Cable with cover electrode monitoring |
Parameters | %RH / °C/°F / °Ctd/ °Ftd/ g/kg / gr/lb / g/m3/ gr/ft3/ ppmV / °Cwb / °Fwb / kJ/kg / mbar / inch H2O / °Ctm (H2O2)/°Ftm (H2O2) / % Vol |
Meas. range |
Humidity / trace humidity | 0 to 100 %RH | -60 to +30 °C td | 0 to 100 %RH |
Temperature | -20 to +70 °C -4 to +158 °F | 40 to +180 °C -40 to +356 °F | -40 to +120 °C -40 to +248 °F | -40 to +180 °C -40 to +356 °F |
Measurement uncertainty* |
Humidity | ±(1.0 + 0.007 * mv) %RH for 0 to 100 %RH / ±(1.4 + 0.007 * mv) %RH for 90 to 100 %RH | ±(1.0+ 0.007 * mv) %RH for 0 to 100 %RH | | ±(1.2 + 0.007 * mv) %RH for 0 to 90 %RH / ±(1.6 + 0007 * mv) %RH for 90 to 100 %RH |
for deviations from media temp. ±25 °C: ±0.02 %RH/K |
Dewpoint | | - ±1 K at 0 °C td
- ±2 K at -40 °C td
- ±4 K at -50 °C td
| |
Temp. at +25°C / +77°F | ±0.15 °C/ 32.2 °F Pt1000 Class AA | ±0.15 °C/ 32.2 °F Pt100 Class A | ±0.15 °C/ 32.2 °F Pt1000 Class AA |