| Operating temperature | -40°C to +85°C (with silicone O-Ring) |
| Storage temperature | -40°C to +85°C |
| Calibration temperature | 20...28°C |
| Relative humidity | 0...100% RH (condensing) |
| Protection degree | IP54 / IP66 / IP68 / type 4X |
| Dimensions | Ø 110 mm |
| Dimensions (HxWxD), stainless steel | 107.4 x 145 x 124 mm |
| Weight approx., stainless steel | 2.8 kg |
| Wire size | 0.13 x1.5 mm2/ AWG 26...16 stranded wire |
| Screw terminal torque | 0.4 Nm |
| Vibration | IEC 60068-2-6 |
| 2...25 Hz | +/-1.6 mm |
| 25...100 Hz | +/-4 g |
| Display resolution | 96 x 64 pixels |
| Number of digits | 5 |
| Backlight | Selectable ON/OFF |
| Backlight color | Selectable white or red |
| Supply voltage, DC | 10 (12 - with backlight)...35 VDC |
| Isolation voltage, test / working | 1.5 kVAC / 50 VAC |
| Response time (programmable) | 1...60 s |
| Signal / noise ratio | > 60 dB |
| Programming | HART |
| Start-up time, transmitter to display | Max. 5 s |
| Long-term stability, better than | +/-0.1% of span / year |
| Accuracy | Better than 0.05% of selected range |
| Signal dynamics, input | 22 bit |
| Signal dynamics, output | 16 bit |
| EMC immunity influence | < +/-0.1% of span |
| Max. offset | 50% of selected max. value |
| RTD type | Pt50/100/200/500/1000; Ni50/100/120/1000 |
| Cable resistance per wire | 5 Ω (up to 50 Ω per wire is possible with reduced measurement accuracy) |
| Sensor current | Nom. 0.2 mA |
| Linear resistance min....max. | 0 Ω...7000 Ω |
| Thermocouple type | B, E, J, K, L, N, R, S, T, U, W3, W5, LR |
| Cold junction compensation (CJC) | Constant, internal or external via a Pt100 or Ni100 sensor |
| Measurement range | -800...+800 mV |
| Min. measurement range (span) | 2.5 mV |
| Input resistance | 10 MΩ |
| Signal range | 4…20 mA |
| Min. signal range | 16 mA |
| Load ( at current output) | ≤ (Vsupply - 10) / 0.023 [Ω] |
| Load resistance, with backlight | ≤ (Vsupply - 12) / 0.023 [Ω] |
| Sensor error indication | Programmable 3.5…23 mA |
| NAMUR NE43 Upscale/Downscale | 23 mA / 3.5 mA |
| Updating time | 440 ms |
| HART protocol revisions | HART 7 and HART 5 |