| Operating temperature | -20°C to +60°C |
| Calibration temperature | 20…28°C |
| Relative humidity | < 95% RH (non-cond.) |
| Protection degree | IP20 |
| Dimensions (HxWxD) | 109 x 23.5 x 104 mm |
| Dimensions (HxWxD) w/ 4501 / 4511 | 109 x 23.5 x 116 / 131 mm |
| Weight approx. | 170 g |
| Weight incl. 4501 / 4511 (approx.) | 185 g / 270 g |
| Wire size | 1 x 2.5 mm2 stranded wire |
| Screw terminal torque | 0.5 Nm |
| Vibration | IEC 60068-2-6 |
| 2…13.2 Hz | ±1 mm |
| 13.2…100 Hz | ±0.7 g |
| Supply voltage, universal | 21.6…253 VAC, 50…60 Hz or 19.2…300 VDC |
| Max. required power | ≤ 2.0 W |
| Isolation voltage, test / working | 2.3 kVAC / 250 VAC |
| Temperature input (0…90%, 100…10%) | ≤ 1 s |
| mA / V input (0…90%, 100…10%) | ≤ 400 ms |
| 2-w. supply (term. 44…43) | 25…16 VDC / 0…20 mA |
| Fuse | 400 mA SB / 250 VAC |
| Programming | Communication enabler 4511 / Programming front 4501 |
| Signal / noise ratio | Min. 60 dB (0…100 kHz) |
| Accuracy | Better than 0.1% of selected range |
| EMC immunity influence | < ±0.5% of span |
| Extended EMC immunity: NAMUR NE 21, A criterion, burst | < ±1% of span |
| RTD type | Pt10/20/50/100/200/250; Pt300/400/500/1000; Ni50/100/120/1000; Cu10/20/50/100 |
| Cable resistance per wire (max.) | 50 Ω |
| Sensor current | Nom. 0.2 mA |
| Effect of sensor cable resistance (3-/4-wire) | < 0.002 Ω / Ω |
| Sensor error detection | Yes |
| Short circuit detection | < 15 Ω |
| Linear resistance min….max. | 0 Ω…10000 Ω |
| Potentiometer min….max. | 10 Ω…100 kΩ |
| Thermocouple type | B, E, J, K, L, N, R, S, T, U, W3, W5, LR |
| Cold junction compensation (CJC) via ext. sensor in connector 5910 | 20…28°C ≤ ±1°C, -20…20°C / 28…70°C ≤ 2°C |
| CJC via internally mounted sensor | ±(2.0°C + 0.4°C * Δt) |
| Δt = | Internal temperature-ambient temperature |
| Sensor error detection | Yes |
| Sensor error current: When detecting / else | Nom. 2 μA / 0 μA |
| Measurement range | 0…20 mA |
| Programmable measurement ranges | 0…20 and 4…20 mA |
| Input resistance | Nom. 20 Ω + PTC 50 Ω |
| Measurement range | 0…12 VDC |
| Programmable measurement ranges | 0/0.2…1, 0/1…5, 0/2…10 VDC |
| Input resistance | Nom. 10 MΩ |
| Relay functions | Setpoint, Window, Sensor error, Latch, Power and Off |
| Hysteresis | 0…100% |
| ON and OFF delay | 0…3600 s |
| Max. voltage | 250 VRMS |
| Max. current | 2 AAC or 1 ADC |
| Max. AC power | 500 VA |
| Sensor error reaction | Break / Make / Hold |
| *of span | = of the currently selected measurement range |
| EMC | 2014/30/EU |
| LVD | 2014/35/EU |
| FM | 3025177 |
| UL | UL 508 |
| EAC | TR-CU 020/2011 |
| DNV-GL Marine | Stand. f. Certific. No. 2.4 |
| EU RO Mutual Recognition Type Approval | MRA000000Z |