| Electrical specifications |
| Environmental conditions |
| Operating temperature | -20°C to +60°C |
| Storage temperatur | -20°C to +85°C |
| Calibration temperature | 20...28°C |
| Relative humidity | < 95% RH (non-cond.) |
Protection degree (Installation in pollution degree 2 & measurement / overvoltage category II.) | IP20 |
| Mechanical specifications |
| Dimensions (HxWxD) | 109 x 23.5 x 104 mm |
| Weight approx | 250 g |
| DIN rail type | DIN EN 60715 - 35 mm |
| Wire size | 0.13...2.08 mm2/ AWG 26...14 stranded wire |
| Screw terminal torque | 0.5 Nm |
| Vibration | IEC 60068-2-6 |
| 2...13.2 Hz | ±1 mm |
| 13.2...100 Hz | ±0.7 |
| Common electrical specifications |
| Supply voltage, universal | 21.6...253 VAC, 50...60 Hz or 19.2...300 VDC |
| Max. required power | ≤ 2.5 W |
| Max. power dissipation | ≤ 2.0 W |
| Isolation voltage - test / working | 2.3 kVAC / 250 VAC |
| Programming | Communication enabler 4511 / Programming front 4501 |
| Signal dynamics, input / output | 20 bit / 18 bit |
| Signal / noise ratio | > 60 dB |
| Bandwidth (3 dB) | > 40 Hz |
| Response time (0...90%, 100...10%) | < 20 ms |
| Input specifications |
| Signal range | ±23 mA |
| Programmable measurement ranges | 0...20 and 4...20 mA ± 10 and ± 20 mA |
| Input voltage drop, nom | 1.4 V @ 20 mA |
| Loop error detection, 4...20 mA | Low detection - < 3.6 mA High detection - > 21 mA |
| Voltage input |
| Signal range | ±12 VDC |
| Programmable measurement ranges | 0...1, 0.2...1, 0...5, 1...5, 0...10, 2...10 V, ±1, ±5 and ±10V |
| Input resistance, nom | 2 MΩ |
| Current output specifications |
| Active unipolar and bipolar mA |
| Programmable ranges | 0-20, 4-20, ±10 and ±20 mA Direct or Inverted action |
| V-curve function, 100-0-100% . | 20-0-20 mA |
| Load, max | 800 Ω |
| Passive 2-wire mA |
| Programmable ranges | 0...20 and 4...20 mA Direct or Inverted action |
| V-curve function, 100-0-100% | 20-0-20 mA |
| External 2-wire loop supply | 3.5...26 V |
| Common specifications current output |
| Signal range | 0...23 mA (unipolar) / -23...+23 mA (bipolar) |
| Current limit | ≤ 28 mA (unipolar) / ±28 mA (bipolar) |
| Load stability | ≤ 0.001% of span / 100 Ω |
| Response time, programmable | 0.0...60.0 s |
| Output limitation at outside range | on 4...20 and 20...4 mA signals - 3.8...20.5 mA on other unipolar signals - 0 and 115% of max. value on bipolar signals - ±115% of min. and max. values |
| Sensor error indication, at 4...20 mA input | selectable - Low, High, Zero or NoneLow - corresponds to 0 mA at 0...20 mA and to 3.5 mA at 4...20 mA High - corresponds to 23 mA at both 0...20 and 4...20 mA Zero - equals 0 mA output None - the output state is undefined |
| Voltage output specifications |
| Programmable ranges | 0/0.2...1, 0/1...5, 0/2...10, ±1, ±5 and ±10 V Direct or Inverted action |
| V-curve function, 100-0-100% | 1-0-1 V, 5-0-5 V and 10-0-10 V |
| Load, min | > 500 kΩ |
| Response time, programmable | 0.0...60.0 s |
| Output limitation at outside range | on unipolar signals starting from 0 - 0 and 115% of max. value on unipolar signals with offset - -5% of min. value and 115% of max. value on bipolar signals - ±115% of min. and max. values |
| Sensor error indication, at 4...20 mA input | selectable - Low, High, Zero or NoneLow - corresponds to the selected min range value High - corresponds to the selected max range value Zero - equals 0 V output None - the output state is undefined |