| GENERAL |
| Sampling Frequency | 128 samples per cycle; 50/60Hz (16 samples/cycle 400Hz) |
| Data Storage Rate | 1 per second (200ms also available on PEL 105) |
| Demand Period Storage Rate | User selectable (1, 2, 3, 4, 5, 6, 10, 12, 15, 20, 30 and 60 minutes) |
Recorded Parameters (Single- and Poly-Phase) | V, I, W, VA, var, PF, Tan, Wh, VAh, varh, THD (V and I), Individual harmonics (from 1 through 50 per phase); Crest Factor (CF), Cos f / DPF |
| Event Log | Tracks and records status changes and error messages along with recorded data |
| Front Panel Indicator LEDs | Bluetooth active, recording in progress, phase connection reversal, overload, battery charging and SD Card status |
| Storage Capacity | SD card included / SD cards up to 32 GB formatted FAT32 are supported |
| Inputs Voltage | PEL 102/103: 4 input channels; PEL 105: 5 input channels via 4mm safety banana jacks |
| Current | PEL 102/103: 3 current input channels ; PEL 105: 4 input channels via custom 4 pin jacks that accept AEMC probes and sensors |
| ELECTRICAL |
| VOLTAGE MEASUREMENT | PEL 105 RANGE |
| 50/60Hz | 42.5 to 69Hz |
| Single-Phase RMS Voltages | 10 to 1000Vrms |
| Phase-to-Phase RMS Voltages | 17 to 1000Vrms |
| 400Hz | 340 to 460Hz |
| Single-Phase RMS Voltages | 10 to 600Vrms |
| Phase-to-Phase RMS Voltages | 17 to 600V |
| DC | 10 to 1000V |
| PT Ratios | - |
| CURRENT MEASUREMENT | 196A*** |
Nominal range for current probes supplied with kit. See chart on pg 11 for other probes | 200mA to 10,000A |
| CT Ratios | Programmable from 1:1 to 25,000:1 (probe dependent) |
| POWER MEASUREMENTS | RESOLUTION |
| Active Power (P)* E= 10^18 | 0.001W |
| Reactive Power (Q)* | 0.001var |
| Apparent Power (S)* | 0.001VA |
| Power Factor | 0.001 |
| Tangent φ (active/reactive power ratio) | 0.001 |
| ENERGY MEASUREMENTS |
| Active Energy (EP) | 1Wh |
| Reactive Energy (EQ) | 1varh |
| Apparent Energy (ES) | 1Vah |
| THD | ± 655% |
| Individual Harmonics | 1 to 50 displayed in percentage; 1 to 7 at 400Hz |
| External Supply | 110V/250V (10%) @ 50/60Hz; 400Hz |
| Power From Phase Measurement | PEL 102/103: requires optional Power Adapter Cat #2137.77; PEL 105: 100V to 1000V ac |
| Back-Up Power Source/Charge Time | Rechargeable 8.4V NiMH battery pack / Approximately 5 hours |
| Battery Life | 30 minutes minimum, 60 minutes typical |
| MECHANICAL |
| Communication Ports | USB 2.0, Ethernet (RJ45), Wireless Bluetooth Class 1 **/ PEL 105 only: Wi-Fi |
| Dimension/Weight | PEL 105: 10.6 x 7.1 x 9.65" (270 x 180 x 245mm) / 8.8lbs (4kg) |
| Case | PEL 105: Polycarbonate UL94 V1 rated |
| DISPLAY |
| Display Type | PEL 105: 4.2 x 3.3" (107 x 84mm), four line, monochrome, backlit LCD with adjustable brightness & contrast |
| ENVIRONMENTAL / SAFETY |
| Operating Temperature/Relative Humidity | EL 105: -4° to 122°F (-20° to 50°C) / 45 to 75%RH |
| Storage Temperature | PEL 105: -40° to 95°F (-40° to 35°C from 0 to 95%HR); -40° to 158°F (-40° to 70°C from 0 to 75%HR) |
| Safety Rating / CE Rating | PEL 105: 1000V CAT IV, Pollution Degree 4 (closed) / Yes |
| Index of Protection | PEL 105: IP67 with cover closed |
| * Maximum value is current probe dependent |