Operating temperature | -40°C to +85°C (with silicone O-ring) |
Operating temperature | -20°C to +85°C (with FKM Oring) |
Storage temperature | -40°C to +85°C |
Calibration temperature | 20...28°C |
Relative humidity | 0...100% RH (condensing) |
Protection degree | IP54 / IP66 / IP68 / type 4X |
Dimensions | Ø 110 mm |
Weight approx., aluminum / stainless steel | 1.3 / 2.8 kg |
Wire size | 0.13 x1.5 mm2 / AWG 26...16 stranded wire |
Screw terminal torque | 0.4 Nm |
Vibration | IEC 60068-2-6 |
2...25 Hz | ±1.6 mm |
25...100 Hz | ±4 g |
Number of digits | 5 |
back light | Selectable ON/OFF |
back light color | Selectable white or red |
Supply voltage, DC: Ex ia, intrinsically safe | 10 (12 - with back light)...30 VDC |
Supply voltage, DC: Other | 10 (12 - with back light)...35 VDC |
Isolation voltage, test / working | 1.5 kVAC / 50 VAC |
Response time (programmable) | 1...60 s |
Signal / noise ratio | > 60 dB |
Programming | HART |
Start-up time, transmitter to display | Max. 5 s |
Long-term stability, better than | ±0.1% of span / year |
Accuracy | Better than 0.05% of selected range |
Signal dynamics, input | 22 bit |
Signal dynamics, output | 16 bit |
EMC immunity influence | < ±0.1% of span |
Extended EMC immunity: NAMUR NE21, A criterion, burst | < ±1% of span |
Max. offset | 50% of selected max. value |
RTD type | Pt50/100/200/500/1000; Ni50/100/120/1000 |
Cable resistance per wire | 5 Ω (up to 50 Ω per wire is possible with reduced measurement accuracy) |
Sensor current | Nom. 0.2 mA |
Linear resistance min....max | 0 Ω...7000 Ω |
Thermocouple type | B, E, J, K, L, N, R, S, T, U, W3, W5, LR |
Cold junction compensation (CJC) | Constant, internal or external via a Pt100 or Ni100 sensor |
Measurement range | -800...+800 mV |
Min. measurement range (span) | 2.5 mV |
Input resistance | 10 MΩ |
Signal range | 4…20 mA |
Min. signal range | 16 mA |
Load (at current output) | ≤ (Vsupply - 10) / 0.023 [Ω] |
Load resistance, with back light | ≤ (Vsupply - 12) / 0.023 [Ω] |
Sensor error indication | Programmable 3.5…23 mA |
NAMUR NE43 Upscale/Downscale | 23 mA / 3.5 mA |
Updating time | 440 ms |
HART protocol revisions | HART 7 and HART 5 |
EMC | 2014/30/EU |
EAC | TR-CU 020/2011 |
EU RO Mutual Recognition Type Approval | MRA0000009 |
ATEX 2014/34/EU | DEKRA 15 ATEX 0058 X |
IECEx | IECEx DEK 15.0039 X |
FM | FM16US0009X / FM16CA0010X |
CSA | 70024231 |
EAC Ex TR-CU 012/2011 | RU C-DK.GB08.V.01316 |
INMETRO | DEKRA 15.0014 X |
NEPSI | GYJ15.1336X, GYJ15.1337X and GYJ15.1338X |
SIL | Hardware assessed for use in SIL applications |