Operating temperature | -20°C to +60°C |
Storage temperature | -20°C to +85°C |
Calibration temperature | 20…28°C |
Relative humidity | < 95% RH (non-cond.) |
Protection degree | IP20 |
Installation in | Pollution degree 2 & measurement / overvoltage cat. II |
Dimensions (HxWxD) | 109 x 23.5 x 104 mm |
Dimensions (HxWxD) w/ 4501 / 4511 | 109 x 23.5 x 116 / 131 mm |
Weight approx. | 250 g |
Weight incl. 4501 / 4511 (approx.) | 285 g / 350 g |
DIN rail type | DIN EN 60715/35 mm |
Wire size | 0.13…2.08 mm2 AWG 26…14 stranded wire |
Screw terminal torque | 0.5 Nm |
Vibration | IEC 60068-2-6 |
2…13.2 Hz | ±1 mm |
13.2…100 Hz | ±0.7 g |
Supply voltage, universal | 21.6…253 VAC, 50…60 Hz or 19.2…300 VDC |
Max. required power | ≤ 1.8 W nom. |
Internal power dissipation | ≤ 2.5 W |
Test voltage | 2.3 kVAC |
Working voltage | 250 VAC (reinforced) / 500 VAC (basic) |
Response time (0…90%, 100…10%) | < 0.75 s |
Programming | Communication enabler 4511 / Programming front 4501 |
Signal dynamics, input | 20 bit |
Signal dynamics, output | 18 bit |
Signal / noise ratio | > 60 dB |
Output referred common mode rejection ratio | 0.02 ppm / VHz |
Accuracy | Better than 0.3% of selected range* |
EMC immunity influence | < ±0.5% of span* |
Extended EMC immunity: NAMUR NE21, A criterion, burst | < ±1% of span* |
of span | = of selected standard range |
Signal range | 0…5 AAC / 40…400 Hz |
Maximum input limit | 6.00 AAC at 40°C |
Programmable measurement ranges | 0…0.5; 0…1; 0…2.5 & 0…5 AAC |
Custom configurable signal range | 0…5 AAC /40…400 Hz |
Min. measurement range (span) | 0.5 AAC |
Input resistance | Nom. < 0.07 Ω |
Signal range | 0…300 VAC / 40…400 Hz |
Programmable measurement ranges | 0…0.5, 0…1, 0…2.83, 0…5, 0…120, 0…230 & 0…300 VAC |
Custom configurable signal range | 0…300 VAC / 40…400 Hz |
Min. measurement range (span) | 0.5 VAC |
Input resistance | Nom. 3 MΩ || 100 pF |
Programmable ranges | 0…20, 4…20 and S4…20 mA ±10 and ±20 mA Direct or Inverted Action |
Load (at current output) | ≤ 800 Ω |
V-curve function, active signals, 100-0-100% | 20-0-20 mA |
Programmable ranges | 0…20 and 4…20 mA Direct or Inverted action |
V-curve function, 100-0-100% | 20-0-20 mA |
External loop supply | 3.5…30 V |
Signal range | 0…23 mA (unipolar) -23…+23 mA (bipolar) |
Current limit | ≤ 28 mA (unipolar) ± 28 mA (bipolar) |
Load stability | ≤ 0.001% of span / 100 Ω |
Response time, programmable | 0.0…60.0 s |
Programmable signal ranges | 0/0.2…1; 0/1…5 ; 0/2…10; 1…0.2/0; 5…1/0; 10…2/0 V ±1, ±5 and ±10 V Direct or Inverted action |
V-curve function, 100-0-100% | 1-0-1, 5-0-5 and 10-0-10 V |
Load (at voltage output) | ≥ 500 kΩ |
Response time, programmable | 0.0…60.0 s |
EMC | 2014/30/EU |
LVD | 2014/35/EU |
RoHS | 2011/65/EU |