Operating temperature | -25°C to +70°C |
Storage temperature | -40°C to +85°C |
Calibration temperature | 20…28°C |
Relative humidity | < 95% RH (non-cond.) |
Protection degree | IP20 |
Installation in | Pollution degree 2 & measurement / overvoltage cat. II |
Dimensions (HxWxD) | 113 x 6.1 x 115 mm |
Weight approx. | 70 g |
DIN rail type | DIN EN 60715/35 mm |
Wire size | 0.13 x 2.5 mm2 / AWG 26…12 stranded wire |
Screw terminal torque | 0.5 Nm |
2…25 Hz | ±1.6 mm |
25…100 Hz | ±4 g |
Supply voltage | 16.8…31.2 VDC |
Fuse | 400 mA SB / 250 VAC |
Max. required power | 1.2 W |
Internal power dissipation | 0.4 W (typ.) / 0.65 W (max.) |
Isolation voltage, test / working | 2.5 kVAC / 300 VAC (reinforced) |
Zone 2 / Div. 2 | 250 VAC |
Temperature input (0…90%, 100…10%) | ≤ 1 s |
mA / V input (0…90%, 100…10%) | ≤ 400 ms |
Signal / noise ratio | > 60 dB |
Programming | ConfigMate 4590 |
Accuracy | Better than 0.1% of selected range |
EMC immunity influence | < ±0.5% of span |
Extended EMC immunity: NAMUR NE21, A criterion, burst | < ±1% of span |
RTD type | Pt10/20/50/100/200/250/300/Pt400/500/1000; Ni50/100/120/1000 |
Cable resistance per wire (max.) | 50 Ω |
Sensor current | Nom. 0.2 mA |
Effect of sensor cable resistance (3-/4-wire) | < 0.002 Ω / Ω |
Sensor error detection | Yes |
Short circuit detection | < 15 Ω |
Potentiometer min….max. | 10 Ω…100 kΩ |
Thermocouple type | B, E, J, K, L, N, R, S, T, U, W3, W5, LR |
CJC via internally mounted sensor | ±(2.0°C 0.4°C * Δt) |
Δt = | Internal temp.-ambient temp. |
Sensor error detection | Yes |
Sensor error current: When detecting / else | Nom. 2 μA / 0 μA |
Measurement range | 0…23 mA |
Programmable measurement ranges | 0…20 and 4…20 mA |
Input resistance | Nom. 20 Ω PTC 50 Ω |
Measurement range | 0…12 VDC |
Programmable measurement ranges | 0/0.2…1, 0/1…5, 0/2…10 VDC |
Input resistance | Nom. 10 MΩ |
2-wire transmitter supply | > 15 V / 20 mA |
Signal range | 0…23 mA |
Programmable signal ranges | 0…20/4…20/20…0/20…4 mA |
Load (at current output) | ≤ 600 Ω |
Load stability | ≤ 0.01% of span / 100 Ω |
Sensor error indication | 0 / 3.5 / 23 mA / none |
NAMUR NE43 Upscale/Downscale | 23 mA / 3.5 mA |
Current limit | ≤ 28 mA |
Signal range | 0…10 VDC |
Programmable signal ranges | 0/0.2…1; 0/1…5 ; 0/2…10; 1…0.2/0; 5…1/0; 10…2/0 V |
Load (at voltage output) | ≥ 10 kΩ |
*of span | = of the currently selected measurement range |
EMC | 2014/30/EU |
LVD | 2014/35/EU |
RoHS | 2011/65/EU |
EAC | TR-CU 020/2011 |
ATEX 2014/34/EU | KEMA 10ATEX0147 X |
IECEx | KEM 10.0068X |
FM | FM17US0004X / FM17CA0003X |
DNV-GL Marine | Stand. f. Certific. No. 2.4 V1-7-2 |
UL | UL 61010-1 |
EAC Ex TR-CU 012/2011 | RU C-DK.GB08.V.00410 |
CCOE | P337347/1 |