| CONTINUITY / RESISTANCE |
| I Rated / Range / Resolution | I > 200mA / 39.99 Ω/ 0.01Ω / ± (1.5% of R + 2cts)12mA / 39.99Ω & 399.9Ω / 0.01 & 0.1Ω /± (1.5% of R + 5cts) with beep |
| Range / Resolution / Accuracy | 4kΩ/ 1Ω / ±(1.5% of R + 5cts) 40kΩ - 400kΩ/ 10Ω - 100Ω /±(1.5% of R + 2 cts) |
| INSULATION |
| Rated Voltage | U test: 50 /100 / 250 / 500 / 1000VDC |
| Range / Resolution / Accuracy | 0.01MΩ to 2GΩ / 10kΩ to 1MΩ / ±(5% of R + 3cts) |
| Short Circuit Current | ≤ 3 mA |
| GROUND |
| 3P GROUNDRange / Resolution / Accuracy | 0.50Ω to 40Ω/ 0.01Ω / ±(2 % of R + 10 cts) 40Ω to 15kΩ /0.1Ω to 1Ω / ±(2% of R + 2cts)15kΩ to 40kΩ / 10Ω/ ±(10% of R + 2cts) |
| Others | Measurement of resistance of auxiliary stakes RH & RS (up to 40kΩ) |
| Ufk | Complies with SEV 3569 |
| 1P SELECTIVE GROUNDRange / Resolution / Accuracy | 0.20 to 39.99Ω - 40 to 399.9Ω / 0.01 – 0.1Ω /±(10% of R + 10 cts) (ISel via clamp) |
| LOOP IMPEDANCE (Zs (L-PE0 AND Zi (L-N OR L-L) – 1P LIVE GROUND |
| Live GroundInstallation Voltage / Frequecy | 90 to 500V / 15.8 to 17.5Hz - 45 to 65Hz |
| High-current mode with TRIPZs (L- PE) & Zi (L- N or L - L)Range / Resolution / Accuracy | Max. test current: 7.5A(0.050) 0.100Ω to 0.5Ω / 0.001Ω/ ±(10% of R + 20cts) 0.5Ω to 3.999Ω / 0.001Ω/ ±(5 % of R + 20 cts) 3.999 to 39.99Ω/ 0.01Ω / ±(5% of R + 2cts) 39.99Ω to 399.99Ω / 0.1 Ω/ ±(5% of R + 2cts) |
| NO TRIP mode (Zs (L – PE) Only) | Test current 6mA – 9mA – 12mA (as required) 0.20 to 0.99Ω / 0.01Ω / ±(15% of R + 10cts) 1.00 to 1.99Ω / 0.01Ω / ± (15% of R + 3 cts)2.00 to 39.99 / 0.01Ω / ± (10% of R + 3cts) 40.00 to 399.9Ω /0.1Ω ± (5% of R + 2cts) 400 to 3999Ω / 1Ω ±(5% of R + 2cts) |
| Calculation of IK short circuit current (PFC (Zs), I Sc PSCC (Zi) | Fault current and short-circuit current: 0.1 to20kA |
| Others | Measurement of the resistive and inductive components of Zs and Zi impedances |
| AC and type RCDs |
| Installation Voltage / Frequency | 90 to 500V / 15.8 to 17.5Hz and 45 to 65Hz |
| IΔn | 10/30/100/500/650/1000 (90V - 280V) or variable ramp and pulse test |
| N-Trip Test | At ½ IΔn – Duration 1000 ms or 2000 ms |
| Ramp Mode | 0.2 to 0.5 x IΔn(Uf) / 0.3 x IΔn to 1.06 IΔn increments of 3.3% x IΔn |
| Trip test: R:Range / Resolution / Accuracy | 0.2 to 0.5 x IΔn(Uf) / 0.5 x IΔn / 2 x IΔn(selective) / 5 x IΔnPulse: 0 to 500ms/0.1 and 1ms / 2ms, Ramp mode: 0 to 200ms / 0.1ms / 2 ms |
| OTHER MEASUREMENTS |
| Current by Current Probe C177A | 5.0mA t0 199.9A |
| Current by Current Probe MN77 | (1mA*) 5.0mA to 19.99A |
| Voltage | 0 to 550VAC/DC / DC and 158 to 500Hz |
| Frequency | 10 to 500Hz |
| Phase Rotation | 20 to 500VAC |
| Active Power | 0 to 110kW single phase – 0 to 330kW three-phaseSimultaneous display of voltage and current waveforms |
| Harmonics | Voltage and Current / up to 50th order / THD-F / THD-R |
| GENERAL SPECIFICATIONS |
| Display | Large 5.7” backlit graphic color LCD 320 x 240 pixels |
| Storage/Communication | USB for data transfer to DataView software (Included) |
| Power Supply | Rechargeable Lithium-Ion 10.8V, 5.8Ah |
| Battery Life | Up to 30 hours |
| Protection | IP 53 / IK04 |
| Dimensions / Weight | 11 x 7.48 x 5.04” (280 x 190 x 128mm) / 4.85 lbs (2.2kg) |
| EMC | IEC61326-1 |
| Electrical Safety | IEC61010-1 – 600V CAT III – 300V CAT IV – IEC 61557 |