Temperature - NTC |
Measuring range | -40.0° to 302.0 °F / -40 to +150 °C |
Accuracy | ±0.4 °F ±1 Digit (-13° to 166.8 °F) / ±0.2 °C ±1 Digit (-25 to +74.9 °C) ±0.7 °F ±1 Digit (-40° to -13.2 °F) / ±0.4 °C ±1 Digit (-40 to -25.1 °C) ±0.7 °F ±1 Digit (75° to 211.8 °F) / ±0.4 °C ±1 Digit (+75 to +99.9 °C) ±0.5 % of mv ±1 Digit (Remaining Range) |
Resolution | 0 °F / 0.1 °C |
Measuring range | -328.0° to 2498.0 °F / -200 to +1370 °C |
Accuracy | ±(0.5 °F + 0.1 % of mv) ±1 Digit / ±(0.3 °C + 0.1 % of mv) ±1 Digit |
Resolution | 0.1 °F / 0.1 °C |
Differential pressure (internal sensor) - Piezoresistive |
Measuring range | -40 to +80 InH2O / -100 to +200 hPa |
Accuracy | ±(0.0 InH2O + 1 % of mv) ±1 Digit (0 to 25 InH2O) / ±(0.3 Pa + 1 % of mv) ±1 Digit (0 to 25 hPa) ±(0.0 InH2O + 1.5 % of mv) ±1 Digit (10.000 to 80 InH2O) / ±(0.1 hPa + 1.5 % of mv) ±1 Digit (25.001 to 200 hPa) |
Resolution | 0.000 InH2O / 0.001 hPa |
Absolute Pressure (internal sensor and external probe) |
Measuring range | 280 to 440 InH2O / 700 to 1100 hPa |
Accuracy | ±1 InH2O / ±3 hPa |
Resolution | 0.1 InH2O / 0.1 hPa |
General technical data |
Weight | 17.99 oz. (instrument) / 510 g (instrument) |
Dimensions | 8.3 x 3.7 x 1.5 in. (LxWxH) / 210 x 95 x 39 mm (LxWxH) |
Operating temperature | 23.0° to 113.0 °F / -5 to +45 °C |
Housing | Plastic |
Protection class | IP40 |
Connectable probes | 4 x digital Bluetooth probe or testo Smart Probe; 2 x digital probe with fixed cable or temperature probe NTC with fixed cable (via Testo Universal Connector - TUC); 2 x temperature probe TC type K with fixed cable |
Product colour | black/orange |
Camera image size | Main camera: 8.0 MP; Front camera: 5.0 MP |
Battery life | approx. 10 hrs continuous operation |
Display type | 5.0" touch display, HD 1280*720 pixels, IPS (160 k) |
Power supply | Rechargeable li-ion battery (5550 mAh) |
Interface | Bluetooth; USB; WLAN |
Memory | 2 GB; 1,000,000 measuring values |
Storage temperature | -4.0° to 140.0 °F / -20 to +60 °C |
Turbulence probe (digital) - wired General technical data |
Storage temperature | -4° to 140 °F / -20 to +60 °C |
Weight | 8.8 oz. / 250 g |
Dimensions | 15.7 x 3.5 x 3.5 in. / 400 x 90 x 90 mm |
Operating temperature | 32° to 122 °F / 0 to +50 °C |
Cable length | 4.593 ft. / 1.4 m |
Probe head diameter | 32.283 in. / 820 mm |
Product colour | black/orange |
Standards | EN ISO 7730 / ASHRAE 55 |
Temperature - NTC |
Measuring range | 32° to 122 °F / 0 to +50 °C |
Accuracy | ±0.9 °F / ±0.5 °C |
Resolution | 0.1 °F / 0.1 °C |
Absolute Pressure |
Accuracy | ±1.2 InH2O / ±3.0 hPa |
Resolution | 0.1 InH2O / 0.1 hPa |
Velocity - Hot wire anemometer |
Measuring range | 0 to 984 fpm / 0 to 5 m/s |
Accuracy | ±(5.91 fpm + 4 % of mv) / ±(0.03 m/s + 4 % of mv) |
Resolution | 1.97 fpm / 0.01 m/s |
Lux probe (digital) - for measuring illuminance, wired Light |
Measuring range | 0 to 100000 Lux 0 to 9300 ftc |
Accuracy | DIN 13032-1 Appendix B F1 = 6 % = V(Lambda) adjustment F2 = 5 % = cos-true evaluation Class C according to DIN 5032-7 |
Resolution | 0.1 Lux (< 10000 ) 1 Lux (> 10000 ) |
General technical data |
Storage temperature | -4° to 122 °F / -20 to +50 °C |
Weight | 3.9 oz. / 110 g |
Dimensions | 4.3 x 2.2 x 0.9 in. / 110 x 55 x 22 mm |
Operating temperature | 32° to 122 °F / 0 to +50 °C |
Cable length | 4.593 ft. / 1.4 m |
Product colour | Black |